Vistaza
WindowsDoorsGlassProjectsKnowledgeProfessionalsChoose yoursSend plans
A dark vent canopy across the head of each window on a finished facade
Trickle vents

We tested it
both ways.

A slot through the head of the frame with a cover that closes from inside, so an apartment gets outside air while the window stays shut and locked.

The question an architect asks

Does the vent cost the window its water rating?

15.66 psf
water penetration, with the vent fitted
15.66 psf
the same window, without it
0.06 cfm/ft²
air leakage, with the vent fitted and closed
Same day
same specimen, same operator

The same window went through ASTM E547 water penetration with the vent fitted and again without it, on the same day. Both passed four five-minute cycles at 15.66 psf (750 Pa) with no leakage. Fitting the vent did not cost the window its water rating.

On a door-and-window assembly the vent made no difference either: the vented build and the unvented build both passed 10.65 psf (510 Pa), and both stopped at the same step above it. The door, not the vent, set the limit.

The air run on the same window was made with the vent fitted and its cover closed. Air leakage was 0.06 cfm/ft². Without the vent, the same window measured 0.00 cfm/ft².

Water and air, with the vent and without it: factory test reports 68/11.2025 and 67/11.2025, 20 November 2025.

The corner of a window cut away at the head, with the vent assembly sectioned
The product

Two aluminum parts over a machined slot.

The head of the frame is machined for the vent on the production line. A ventilator goes on inside and a canopy outside, bedded in sealant and screwed to the frame. It is not in the sash, so it works the same on a fixed light and on a window that opens.

Air comes in above head height, so it mixes with room air before anyone feels it. The resident opens and closes the ventilator from inside; closed, it seals against a compression gasket. Outside, the canopy sheds rain off the opening and keeps the slot out of the weather, and it is finished to the frame color.

SeriesVi5 · Vi6 · Vi5 sliding door
TypesFixed and operable alike
WhereFrame head — never the sash
Length464 mm (18-1/4″)
Adds to the head33 mm (1-5/16″), inside and out
OrderingBy request, with the window
From outside

All that shows is the canopy.

One slim canopy at the head of the frame, in the frame color. Air enters through its slotted underside, which faces down, so rain running off the wall and the head passes over it.

The ventilator and its control are inside the room. Nothing on the facade opens, closes or moves.

A black vent canopy across the head of a black window frame, seen from below
Where it sits

At the head, above the glass.

The section an architect wants for the head detail, and the one that goes on the shop drawings. It is approved with the window.

The head in section: fixed unit on the left, casement on the right. The ventilator inside, the canopy outside, the machined slot through the uPVC frame between them.
The head in section: fixed unit on the left, casement on the right. The ventilator inside, the canopy outside, the machined slot through the uPVC frame between them.
The same head on the Vi6: fixed unit on the left, casement on the right. The air path runs straight through the deeper frame, clear of the steel reinforcement.
The same head on the Vi6: fixed unit on the left, casement on the right. The air path runs straight through the deeper frame, clear of the steel reinforcement.

Because the slot is machined at the factory, the vent has to be in the order. It is not something to add to a finished frame on site — cutting a finished frame puts its chambers and its drainage paths at risk.

Why New York projects ask for one

The acoustic rating only counts while the window is shut.

On a noise-mitigated building the Noise Installation Report has to show how the apartment gets air without opening the window. That is what the trickle vent is doing on most of our New York projects.

The model named in that report has to be the model that gets installed. Settle it before the shop drawings are approved: tell us the vent the acoustic report names and we will confirm what we can supply against it.

What we do not publish, and why.

We do not print a free area or an airflow for this vent, because no certified figure exists for it. If the ventilation design needs one, ask us and we will get it in writing rather than estimate it.

No Vistaza sound test has been run with a vent in. The STC and OITC on this site are for the window as it was tested, without one. A vent is a deliberate opening through the head, so the acoustic consultant has to account for it — give us the required Dn,e,w and we will match the vent to it.

Trickle vent canopies at the heads of the windows on a finished building
Trickle vent canopies at the heads of the windows on a finished building
Trickle vent canopies at the heads of the windows on a finished building
On a building

All three of these buildings carry trickle vents: a dark canopy at the head of each window, over the sash that opens. The first two went through a Noise Installation Report to get them.

Does your noise report call for vents?

Send it with the plans and the window schedule. We match the vent to the openings it names.

Send plans

Send plans